DIGITAL
NON-PROGRAMMABLE
THERMOSTAT
8
401
ELECTRIC
E
GAS
G
OIL
O
®
NeW
1 Heat / 1 Cool
User's Manual
Quick Start
Installation
HEAT PUMP
H
Application
The Robertshaw 8401 is a single-stage thermostat designed to control
24 VAC gas or electric heating and cooling systems or single-stage heat
pump. The 8401 requires the use of a common wire.
Features
Large backlit display
Adjustable temperature differential: 1°F to 3.0°F (0.5°C to 1.5°C)
Compressor short cycle protection
Accuracy within ±1°
Zone system compatible as a master thermostat
Permanent memory retention
Fahrenheit/Celsius display option
Adjustable from 45°F to 90°F (7°C - 32°C)
Quick wire terminal block
1
110-1087B
110-1087B.qxd 3/4/05 4:00 PM Page 1
Vue de la page 0
1 2 3 4 5 6 ... 11 12

Résumé du contenu

Page 1 - User's Manual

DIGITAL NON-PROGRAMMABLE THERMOSTAT8401ELECTRICEGASGOILO®NeW1 Heat / 1 Cool User's ManualQuick StartInstallationHEAT PUMPHApplicationThe Robertsh

Page 2 - Recycling Thermostat

10♦ Check Filter ResetOnce the filter timer has expired,CHECK FILTER will turn on and stayon. To clear the message and resetthe timer:1. Press the a

Page 3 - WARNING:

Step 5: TroubleshootingSymptom Remedy 11Thermostat does not turn on system.Check wiring (see Installationsection). If problems with thermostat cannot

Page 4 - Figure 4

12Two Year Limited WarrantyInvensys Controls Americas warrants to the original contractorinstaller, or to the original consumer user, each new Roberts

Page 5 - Wiring Diagrams

WARNING:• Always turn off power at main fuse or circuit breaker panel beforeinstalling, removing, cleaning, or servicing thermostat.• Read all the inf

Page 6 - Wiring Diagrams (continued)

WARNING:In heat pump applications, do not connect anything to the W1terminal. When switched to HP mode, W1 is connected internallyto Y1 on the thermo

Page 7 - TERMINAL LEGEND - 8401

4. Remove the cover using a coin or screwdriver (Figure 3). Set aside.5. Place thermostat against the wall at desired location. Make surewires will fe

Page 8

5HotHeatingControlCoolingControlTransformerTHERMOSTATW1CRY1GOB24 VAC120 VACHEAT/COOL4-WIRESINGLE TRANSFORMERFanControlHotHeatingControlTransformer24 V

Page 9 - ♦ Temperature Differential

6HotCoolingControlFanControlTransformer24 VAC120 VACCOOL ONLY3-WIRESINGLE TRANSFORMERW1Y1GTHERMOSTATOBCRHotCompressorContactorTransformer24 VAC120 VAC

Page 10 - Backlit Display

713. Make sure wire connections are secure.14. Push excess wire back through opening.15. Set the Electric/Gas switch to either GAS for a gas/oil heati

Page 11 - Step 5: Troubleshooting

8Step 3: Testing the ThermostatWARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILLDAMAGE THE T

Page 12 - United States of America

9Step 4: Customizing the Thermostat♦ SettingsSystemCool: The thermostat controls the cooling.Off: The heating and cooling systems are off.Heat: The th