Robertshaw 9801i2 Manuel d'utilisateur

Naviguer en ligne ou télécharger Manuel d'utilisateur pour Thermostats Robertshaw 9801i2. THERMOSTATS - Robertshaw Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 96
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 0
THERMOSTATS
Robertshaw
®
proprietary and confidential ©2014 1
Vue de la page 0
1 2 3 4 5 6 ... 95 96

Résumé du contenu

Page 1 - THERMOSTATS

THERMOSTATS Robertshaw® proprietary and confidential ©2014 1

Page 2

– Conventional Heat Pump • No control at air handler • Thermostat controlled – Gas Furnace • Plenum switch • Electronic furnace control • Furnace c

Page 3 -  Residual Fan

 Typical fan selections are:  On  Auto  Intermittent  On provides 24 / 7 continuous fan activated  Auto provides fan when air handler is on in h

Page 4 -  G = Fan

• Advantages of Intermittent Fan • Improve comfort with constant moving air • Less cost due to less compressor run time • For example, on 10 minute

Page 5 - – Blower motor

Residual Fan – Applied to forced air systems only – Allows fan to run after a call for either heating or cooling • Pulls built up HVAC heat or cool in

Page 6

 Continuous Fan is minimal kWh usage  Energy saving on Furnace Blower is worth monetary savings  Opportunities to Save Energy:  Zoning  Indoor Ai

Page 7 -  Not needed by some systems

 Staging is a control feature where a higher or lower power consumption level of heating or cooling is enabled  Staging can be automatic or manual 

Page 8 -  Inside

 Humidity adds moisture to the air during a heat call  Dry air can cause dry skin and discomfort  Adding humidity makes the air more comfortable 

Page 9 -  Living Room

 Differential is the difference between the set point and the maximum allowed deviation from set point before the system calls for Heating or Cooling

Page 10 - – MilliVolt

 Balance Point control is used to turn OFF inefficient equipment and turn ON more efficient equipment

Page 11 -  Intermittent

• Enthalpy - Total amount of heat in one pound of substance calculated from accepted temperature base, expressed in BTUs per pound mass • Enthalpy of

Page 13 - Residual Fan

Enthalpy Changeover Setpoint The A,B,C,D enthalpy setpoints adjust enthalpy changeover characteristics. The “A” setting provides the greatest energy

Page 14 -  Indoor Air Quality

•MECHANICAL •ELECTRONIC © Invensys 2012 Invensys proprietary & confidential

Page 15

Mechanical Thermostats – Bi-metal thermometer • Strip of two different metals (iron and copper) • Each metal has a different response to temperature •

Page 16

Digital Non-Programmable – Equivalent to mechanical thermostat – Solid-state operation • No mechanical wear • Elimination of expensive metals – Can co

Page 17

Digital Programmable – Adds ON/OFF schedules – Reduces energy use when comfort is not critical – Normally 4 periods per day • Morning • Day • Evenin

Page 18

– Offers ability to sense temperature in locations away from thermostat • Outside • Other indoor spaces (such as bedroom) – Sensors can be used for in

Page 19

•RF •ZIGBEE® •WI-FI •RUBEE® © Invensys 2012 Invensys proprietary & confidential

Page 20

• Improves ease of retrofit • Adds flexibility • Reduces cost of multiple zone management • Enables remote support

Page 21 - •ELECTRONIC

Pros • Long Distance • Industry History Cons • Higher frequencies require higher power consumption • Interference concerns

Page 22 - – Bi-metal thermometer

Pros • Self discovering • Long distance • Mesh Network Cons • Power requirements high • Infrastructure can be costly Mesh Network

Page 23 - Digital Non-Programmable

 Short Cycle Delay  Remote Sensors  Time of Day Zoning  Residual Fan  Intermittent Fan  Staging  Humidity Controls  Differentials  Balance Po

Page 24 -

1. Devices join utility network 2. Demand Response events • Consumer can opt ‘in’ or ‘out’ 3. Load Control events 4. Pricing messages • Unsecured to

Page 25 - • Outside

Pros • Cost • Industry Standard • Internet Connectivity Cons • Security • Interference Concerns

Page 26 - © Invensys 2012

Pros • Less interference • Less power • Packet based • IEEE 1902.1 Cons • Limited distance • Slower communication speed

Page 27 - • Enables remote support

Internet Thermostat Controller web page for PC/Mac and smartphone At-a-glance energy usage on iPhone Internet hub to wireless gateway Integration wi

Page 28

• Advanced systems monitor power usage by circuit • Creates energy profiles • Can help identify problem appliances and sources early Heat Pump Refrige

Page 29 - Mesh Network

• Wall Units • Internet • Smart Phone © Invensys 2012

Page 30 - 3. Load Control events

Technology – Open protocols (ZigBee®, Wi-Fi, etc.) – Smart-grid integrated controls – Adaptive predictive controls algorithms – Touch-screen interacti

Page 31

• Ability to monitor remotely • Ability to control remotely

Page 33 - Internet

•MONITORING •TARIFF / RATE FLEXIBILITY •CONTROL © Invensys 2012 Invensys proprietary & confidential

Page 34 - • Creates energy profiles

 W1 = 1st stage Heating  W2 = 2nd Stage Heating  E = Emergency Heating  Aux = Auxiliary Heating  Y = Heat pump Heating  G

Page 35 - • Smart Phone

• Simplify meter reading • Enhance data collection efficiency • Reduce manpower costs

Page 36

• Differences in rates based on usage and time of day • Rate flexibility depends on total usage • Rate incentives for utility control of energy usage

Page 37

• Complete energy control by utility or municipality • Better distribution of energy resources • More reliable supply overall

Page 38

• From creators of Apple’s iPod - next generation thermostats

Page 39 - •CONTROL

• Launched in 1990 by U.S. EPA • Originally targeted power plants in attempt to lower energy consumption and greenhouse gas emissions • Expanded to la

Page 40 - • Simplify meter reading

• New designation to identify products that contribute to energy conservation • Replacement term for products previously labeled Energy Star • Identif

Page 42

Robertshaw® i2 Deluxe Series • Setup Wizard in multi-languages (English, Spanish and French) • Humidity Control • Independent remote and outdoor senso

Page 43

WALL THERMOSTAT

Page 44

Contractor ID Feature Set your name and phone number in the display to remind customers to call you for service. Conversational Menus Take the progra

Page 45

• Cooling Air Conditioning System Components – Condenser – Evaporator – Compressor – TXV – Blower motor – Heater – Receiver – Drier – Fan

Page 46

9801i2  1 Heat / 1 Cool  Menu Driven Display  Set-up Wizard  Humidity Control  Temperature override  10 minutes to 365 days 9825i2  Same as a

Page 48 - WALL THERMOSTAT

• Robertshaw RS 2000/3000 Economy Series • Adjustable Temperature Differential • Worry-Free Memory Retention • Low Temperature Freeze Protection • Fil

Page 49

Note the Light symbol. Differentiates RS3110 cover from other Economy series

Page 50 -  Humidity Control

• Bigger, Brighter Display with blue backlight • Adjustable Temperature Differential • Automatic Compressor Short Cycle Protection • Separate “O” and

Page 52

• Pop-up Wizard • Engineered True Blue backlight display • Largest Temperature Display Character Size • Soft Touch Keys • Set-up Test Mode • Auto Chan

Page 54

i2 Series

Page 55

RS456 Series

Page 56 - • Easy Change Battery Access

 Anticipation – the activation or deactivation in advance of ambient temperature reaching set point  Energy Efficient Recovery – thermostat to initi

Page 57

RS2000 Series RS3000 Series

Page 58

Competitive Comparison Robertshaw® Honeywell White Rodgers Family Model or SKU 97xxi2 & 98xxi2 TH8000 1F90 Series Menu-driven operation Ye

Page 59

Pros and Cons Invensys Controls Competition Menu-driven operation Dot Matrix Display allows for common language programming, ease of use & insta

Page 60 - RS2000 Series RS3000 Series

Value Proposition Wholesaler / Distributor Contractor End-User Menu-driven operation Easier to sell Easy Installation Easier to Understand and use

Page 61 - Competitive

Features Robertshaw® Honeywell White-Rogers Braeburn Family Model or SKU RS4000/RS5000 RS6000 TH5000 TH6000 1F80 series 3000/5000 Auto Changeove

Page 62 - More energy costs

Pros and Cons Invensys Controls Competition Auto Changeover Better comfort in Spring and Fall More trips to the stat Pop-Up Wizard Programming Sim

Page 63 - Contractor End-User

Value Proposition Wholesaler / Distributor Contractor End-User Auto Changeover Less SKU’s on shelf Less programming Greater Comfort Pop-Up Wizard Pr

Page 64 - Yes Yes Yes Yes

Competitive Comparison Robertshaw® Honeywell White/ Rodgers Braeburn Family Model or SKU RS2000 / RS3000 TH1000 / TH2000 TH3000 / TH4000 1F70 ser

Page 65 - Requires separate

Pro’s and Con’s Invensys Controls Competition Larger Display & Characters Easier to See and Read Smaller Characters Filter Monitor Convenient R

Page 66

Value Proposition Wholesaler / Distributor Contractor End-User Larger Display & Characters Easier to Sell Easier to read & Set-up Easier to r

Page 67 - Yes No No No

 Protection of compressor to reduce excessive cycling  Adjustable 0 to 5 minute short cycle delay  Usually 1 minute increments  Applied after call

Page 69 - Proposition

Displayed Choice Default SCAL F° or C° F° CLOC 12 or 24 hour 12 LITE 1=always on, 0=off 0 DIFF Set Differential, 0.5-3 F° or 0.5-1.5 C°

Page 70

• Press Fan and HEAT/COOL buttons together for 10 seconds Press at same time

Page 71

• Press FAN and HEAT/COOL buttons for 10 seconds • Press the HEAT/COOL button to turn on heat. A second press will turn on 2nd stage of heat • Contin

Page 72 - Press at same time

• Press the UP and DOWN buttons simultaneously for 3 seconds • Pop-Up Menu will initiate

Page 73 - • To exit the test mode for:

• Press DOWN and HEAT/COOL buttons simultaneously – Hold for 10 seconds • A lock will appear in the – Upper left hand corner of the RS4000 series –

Page 74 - • Pop-Up Menu will initiate

– C: 24 VAC Common – R: 24 VAC – Y1: 1st stage cooling – E/W1: Emergency heat / 1st stage heating – W2: 2nd stage heating – Y2: 2nd stage cooling – L:

Page 76 - – G: Fan

Power may be provided by either (Dual Power) • 24 VAC • 2 (AA) Batteries • Thermostats with batteries and powered by 24V AC will continue to functio

Page 77

• There is NO HEAT! Switch on side of furnace  Most furnaces will have an ON/OFF wall switch next to them Fuses and/or circuit breaker  Make sure fu

Page 78

 Protection of compressor to reduce excessive cycling  Remote sensors sense temperature in different spaces  Outside  Inside  Sensors serve as c

Page 79 - Switch on side of furnace

• There is NO HEAT! Thermostat settings  Is thermostat in HEAT mode and calling for heat? Wiring  Is thermostat wired properly and is jumper there?

Page 80 - • There is NO HEAT!

• Overview Catalog in Spanish…150-2284 • Thermostat Catalog in Spanish…150-2208

Page 81

• Order Sell Sheets 150-2317 and 150-2318

Page 82

• Order Sell Sheets: 150-2089, 150-2090 and 150-2091

Page 83

• Order Sell Sheets: 150-2080 & 150-2082

Page 84

What is activated when UP and DOWN buttons are pushed simultaneously for 10 seconds? a) Password Setup b) System Test Mode c) Pop-Up Menu d) Auto chan

Page 85

Robertshaw® RS456 Series Wall Thermostats are powered by: a) 24 Volts AC and/or AA Batteries b) Line Voltage and/or AAA Batteries c) Line Voltage only

Page 86

I2 SERIES WALL THERMOSTAT

Page 87 - I2 SERIES WALL THERMOSTAT

 Setup Wizard  Language  Time and Date  Time Format (12 or 24 hours)  Auto Adjust Daylight Savings Time  Temperature Scales (°C or °F)  Set Sch

Page 88 -  Fan Settings

System Settings  Equipment Setup  Residual cooling  Balance points  Limits  Auto changeover  Contacts  User Security (code is 4199)  System se

Page 89 -  Contacts

 Time of Day Zoning allows user to prioritize the temperature in a room during a selected event  Depends on Rooms:  Upstairs vs. Downstairs  Basem

Page 90 -  Set Relative Humidity %

 Humidity (9800 series only)  Dehumidity (9800 series only)  Set Relative Humidity %

Page 91 -  2nd Stage Heat Equipment

 1st Stage Heat Equipment  None, Furnace, Strip or Heat pump  2nd Stage Heat Equipment  None, Furnace, Strip or Heat pump  Enable Auto Changeover

Page 92

Exercise 1  12 hour, F, 1 Heat/1 Cool, Strip heat  Fan ON continuous Exercise 2  24 hour, C, 2 Heat/ 2 Cool, Heat Pump, Furnace  Fan ON 10 min, F

Page 93 - 9725i2 same except

9801i2 Wiring 9825i2 Wiring 9725i2 same except 9701i2 same except

Page 94

– C: 24 VAC Common – R: 24 VAC – Y1: 1st stage cooling – E/W1: Emergency heat / 1st stage heating – W2: 2nd stage heating – Y2: 2nd stage cooling – L:

Page 95 - Websites:

Telephones: Technical Service 1-800-445-8299 Technical Service Fax 1-630-260-7294 Customer Service 1-800-304-6563 Customer Servi

Commentaires sur ces manuels

Pas de commentaire